Technical Parameters |
|
|
Compliant with Standards |
EN/IEC 61000-4-5、GB/T 17626.5 |
|
Pulse Voltage |
Up to 10.0kV (1.2/50 μs) |
|
Pulse Current |
Up to 5.0kA (8/20 μs) |
|
Phase Synchronization |
Superposition of arbitrary line-line and line-ground phase angles |
|
Coupling Path |
L1、L2、L3、N、 Any combination of paths along the route L1 (DC+), N (DC -) DC path |
|
Coupling Switching Method |
Automatic switching and scheduling function |
|
Coupling Capacitor |
9 μF (line-ground), 18 μF (line-line) |
|
Coupling Resistance |
10 Ω (line-ground), 0 Ω (line-line) |
|
Residual Pulse Voltageat EUT Injection End |
Not exceeding 15% of the applied test pulse voltage or twice the peak rated voltage of the coupling/decoupling network |
|
EUT Carrying Capacity |
DC 1500V 400 A、AC 1000V 400A |
|
EUT Power Switching Method |
Automatic switching |
|
Rated Current and Waveform Parameters |
I ≤ 400 A, waveform parameters meet the full current range |
|
General Parameters |
|
|
Scope of Working Power Supply |
AC 220 V (±10%),50 Hz /60 Hz (±5% ) |
|
Fuse |
10A |
|
Maximum Power Consumption |
500 W |
|
Auxiliary Interface |
D-sub 25p |
|
Instrument Working Status Indication |
Front panel LED indicator |
|
Instrument Grounding Connection method |
Use a flat grounding wire |
|
Cabinet Size |
800 × 1200 × 1450mm (length × width × height) |
|
Weight |
About 700 kg |
|
Ambient Temperature |
15℃ ~35℃ |
|
Relative Humidity |
45% ~75% |
|
Atmospheric Pressure |
86 kPa ~ 106 kPa |
|
Standard Accessories |
|
|
Three Core Power Cable, 25 Core Data Cable, Instruction Manual, Test Cable, Grounding Wire, Fuse. |
|
|
Optional Accessories |
|
|
CWS 600X |
Combination wave lightning surge simulator, meeting the IEC 61000-4-5 standard, with a maximum pulse output of 6.0kV (1.2/50 μs) and 3.0kA (8/20 μs) |
|
CWS 800X |
Combination wave lightning surge simulator, meeting the IEC 61000-4-5 standard, with a maximum pulse output of 8.0kV (1.2/50 μs) and 4.0kA (8/20 μs) |
|
CWS 1000X |
Combination wave lightning surge simulator, meeting the IEC 61000-4-5 standard, with a maximum pulse output of 10.0kV (1.2/50 μs) and 5.0kA (8/20 μs) |
|
CCS 600X |
Combination immunity tester, meeting the IEC 61000-4-5 standard, with a maximum pulse output of 6.0kV (1.2/50 μs) and 3.0kA (8/20 μs) |
|
VCF-80 |
High voltage differential probe, maximum test voltage 8kV,attenuation ratio 1000:1, meets the open circuit voltage waveform calibration of lightning surge instruments |
|
CM 0302M |
Broadband current monitoring clamp, testing short-circuit current of 0.001 V/A |